The Cybersecurity and Infrastructure Security Agency has issued an industrial control systems advisory detailing several vulnerabilities in Dorsett Controls InfoScan software. According to the alert published by CISA, successful exploitation of these flaws could allow an attacker to obtain sensitive system information, access application data without authorization, recover stored credentials, or intercept and manipulate network communications.

The issues affect InfoScan versions 1.45.0 and earlier. Dorsett Controls, a U.S.-based vendor whose solutions are deployed globally, provides control and monitoring technologies primarily used within the critical infrastructure space, specifically the water and wastewater systems sector.

Overview of the Vulnerabilities

The advisory outlines multiple security weaknesses spanning certificate validation, exposure of sensitive configuration data, hard-coded cryptographic keys, and missing authentication controls. The most severe issue is tracked as CVE-2026-117659, which received a CVSS v3.1 base score of 8.1 and a CVSS v4.0 score of 8.5.

CVE-2026-117659 stems from improper TLS certificate validation within the InfoScan Electron desktop client. The client fails to validate the trustworthiness of certificates, accepting them without proper verification. Furthermore, the application configures its underlying Electron framework with weakened security boundaries, specifically leaving nodeIntegration enabled while setting both contextIsolation and webSecurity to disabled. An attacker capable of intercepting network traffic can present an untrusted certificate without the application rejecting the connection.

A second vulnerability, tracked as CVE-2026-120157 with a CVSS v3.1 score of 5.3, involves the exposure of sensitive system information. The publicly distributed InfoScan Electron installer contains configuration files that reveal hostnames belonging to customer installations as well as internal development, testing, and database infrastructure. Anyone who inspects the installer can extract these hostnames without prior authentication.

Credential Exposure and Unauthenticated Access

The software also suffers from cryptographic flaws. Under CVE-2026-120255 (CVSS v3.1 score of 4.3), InfoScan relies on hard-coded cryptographic keys and initialization-vector values for database encryption. The application uses these static values to encrypt MongoDB passwords before saving them into the Windows registry. Because the keys reside directly in the distributed code, an individual who acquires the encrypted registry value can recover the plaintext database password.

Additionally, CVE-2026-120260 involves missing authentication on an endpoint used to retrieve sales-automation templates. A local user can send an unauthenticated HTTP request to this endpoint to access template data without requiring a valid session.

CISA noted that the advisory also addresses weaknesses related to the generation of error messages containing sensitive information, all impacting versions 1.45.0 and prior.

Affected Systems and Patch Information

Organizations operating Dorsett Controls InfoScan deployments at version 1.45.0 or below are urged to upgrade. Dorsett Controls has addressed the issues and recommends updating installations to version 1.46 or higher.

For connected environments, administrators can apply the fix directly through the software. After logging in, administrators should navigate to the menu, select System Maintenance, click Check for Updates, and then use the Install Now button within the Ready To Install section.

For air-gapped or offline installations that lack direct internet access, administrators must obtain the update manually. The vendor instructs operators to log into the Dorsett Controls Customer Portal, select the InfoScan Update tile, download the update package, and follow the provided instructions to complete the offline deployment.

What You Should Do

Asset owners and defenders supporting water and wastewater infrastructure should take immediate steps to reduce risk:

  • Verify the currently running version of InfoScan across all operator workstations and servers.
  • Apply the update to InfoScan version 1.46 or later using either the automated updater or the customer portal for isolated systems.
  • Ensure that industrial control workstations and SCADA networks remain isolated from general corporate networks and untrusted internet access.
  • Audit existing Windows registry keys and database accounts to ensure MongoDB instances have robust, unique credentials and are not accessible from unauthorized segments.